Burner control
On-site housing for controlling, igniting and monitoring
pulse-controlled, modulating or step-controlled
gas burners. For
continuous operation with ionization monitoring or
UV monitoring with
UVD UV probe. Intermittent operation with UV probe
UVS. Display of the
program status, the device parameters and the
flame signal.
Manual operation mode. Diagnosis and setting of the
device parameters via
optical interface and PC software BCSoft.
EU-certified, FM and
EAC approved, certified for systems up to SIL 3
(corresponds to PL e).
Series: Version for ignition and main burners
Mains voltage: 230 V~, 50/60 Hz
Ignition transformer: 8 kV, 12 mA, ED 100%
Flange plate: M32
Valve monitoring system: Without
High temperature operation: Without
Input function: Without
Pressure switch: Without
Connection plug: With screw terminals
Packaging: Individual packaging
Power supply: Via safety chain
Power module: Power module
Series: 400
Mains voltage: 230 V~, 50/60 Hz
Air actuator: With air valve control
Optional output: Without
Power supply: Via safety chain
I004 Flame monitoring: Ionization
I050 Function contact 80, 81/82: Fault message
I051 Function contact 90, 91/92: Ready message
I052 Function contact 95/96: Burner 1 operating message
I053 Function contact 95/97: Burner 2 operating message
I054 Function contact 85/86, 87: Air message
I061 Function terminal 1: Start 1
I062 Function terminal 2: Reset
I063 Function terminal 3: Purge
I064 Function terminal 4: Air
I065 Function terminal 5: Start 2
I068 Function terminal 35: Safety chain
A001 Burner 1 shutdown threshold: 2 micro A
A002 Burner 2 shutdown threshold: 2 micro A
A003 External light test: In standby
A007 Burner 1 start-up attempts: 1
A008 Burner 2 start-up attempts: 1
A093 Pre-ignition time tVZ: 0 s
A094 1st start-up safety time: 5 s
A095 Flame stabilization time 1 tFS1: 0 s
A096 2nd safety time start-up: 3 s
A097 Flame stabilization time 2 tFS2: 0 s
A078 Burner application: Burner 1 and burner 2
A079 Ignition burner: Externally controlled
A009 Restart: No
A074 Combustion operating mode: Flame operation
A043 Run-on: Off
A039 Run-on duration: 0 s
A048 Air actuator control: Opens when externally controlled
A129 Active cooling outputs: Air actuator
A041 Run time selection: On, for moving to the positions
for
minimum/maximum power
A042 Run time: 1 s
A049 Air actuator when starting up: Cannot be controlled externally
A050 Air actuator in the event of a fault: Can be controlled externally