IPL244/C ELECTRICAL NETWORK ANALYSER
Loreme
Assy - Built in enclosure: 144 x 144 x 175 mm
Measurement - DC measure: Voltage, Amp, Power
- AC measure: Voltage, Amp, Frequency, Cos phi
- Active, reactive & apparent power
- Active energy: consumed & generated
- Reactive energy: inductive & capacitive
- Unbalanced & Balanced three phases network, with or without
Neutral
- IT & PT ratio setting
Inputs - 3 voltage inputs:
0...125 Vac, +/- 175 Vdc, 0...500 Vac, +/- 700 Vdc
- 3 amp inputs:
0...1 Aac, +/- 1 Adc, 0...5 Aac, +/- 5 Adc
- Frequency: 40...400 Hz
- Operating inputs:
* Voltage: By your own
* Current : By your own
*TP: 1450
* TI: 1,000
Display - 8 displays with 3 digits ½ LED, 7 segments
& 2 displays with 7 digits LED, 7 segments
- Selection by pushbutton of values to be displayed
Power supply - 20...70 Vac/dc or 80...265 Vac/dc
- Operating power supply: 230 Vac
Isolation - Power supply/Inputs: 1500Vac
Setting - USB link (USB cable as option)
Option Slot 1 - Analog output :4...20 mA → 0...200 MW
(To be confirmed)
Option Slot 2 - Analog output :4...20 mA → -150...+150 MW
Option Slot 3 - Analog output :4...20 mA → 0...200 MW
(To be confirmed)
Option Slot 4 - Analog output :4...20 mA → -150...+150 MW
Option Slot 5 - Analog output :4...20 mA → 45...55Hz
Option Slot 6 - Analog output: 4...20 mA (spare)
Option Slot 7 - None
Option Slot 8 - RS485 Modbus communication
ALSTOM execution - RS232 Sub-D9 pins connector at rear
- 3x intensity wiring on spring rods at rear