PureLine D AF 0016
Hanovia
Description
UV system complete with 316L stainless steel chamber, control cabinet, UV sensor and PN16
flange connections.
design data
Application: disinfection
Type of water: drinking water
Pre-treatment: filter (recommended)
i) flow rate 70 m³/h
ii) UV transmission (T 10) 90% (assumed)
iii) UV dose 60 mJ/cm² RED at the end of the
lamp life
iv) UV lamp type Hanovia low-pressure amalgam lamp
v) Power consumption per heater 270 W
vi) Number of radiators 1
vii) Expected lamp life 12,000 hours
viii) Material UV chamber stainless steel 316L / 1.4404
ix) Connections 2” (DN 50) PN16 flange
x) Operating pressure 10 bar
xi) Control cabinet material Polyester coated carbon steel
xii) Supply voltage 230V ±10% / 115V ±10% - 50/60 Hz
xiii) Standard cable length 5 m