DC UPS system 400 V AC to 24V DC / 20A
The battery-buffered DC power supply of the AKKUTEC series works according to the stand-by parallel principle and, in conjunction with a lead-acid battery, ensures that the DC voltage supply is maintained in the event of a power failure.
The DC UPS is characterized by the following properties:
primary switched-mode power supply with I/U charging characteristic
active power factor correction (PFC)
Microcontroller based battery management
Temperature tracking of the charging voltage by external sensor module (option)
Display and control panel for control cabinet door installation or surface-mounting (option)
Designation AKKUTEC 2420-0
Rated input voltage 3 x 400 - 500 V AC -15% +10%
Rated frequency 50/60 Hz
Max input current rating 1.4A AC
Rated output voltage 24 V DC
Output voltage range (with temperature tracking) 19.8 V DC ... 27.8 V DC
Output voltage range (without temperature tracking) 19.8 V DC ... 26.8 V DC
Control inputs referenced to +24VDC
Shut down
boost charge
Max. rated output current 20 A DC
End-of-charge voltage with temp. sensor at 25° 27.8 V DC ± 0.4%
End-of-charge voltage without temp. sensor 26.8 V DC ± 0.4%
Max. charging current 2 A at 100% load
Charging current at 0% load 21 A
Battery type Pb rechargeable battery, maintenance-free
Buffer time Depending on the battery
Degree of protection IP 20
Operating temperature 0 ... 40 °C
Storage temperature 0 ... 50°C
Max. installation altitude (without derating)
Dimensions (H x W x D) 101 x 241 x 244 mm
Weight approx. 2.4 kg
Standards and regulations EN 50178 / EN60950