Liquid chiller model ACW-LP 45
Nominal cooling capacity: 5300 W (liquid +22°C,
ambient +32°C)
Cooling: recommended Eurogreen 132 Nano
Cooling gas Freon: R410A
Outlet water temperature between +15°C and +30°C
Max. inlet water temperature: +40°C
Max. ambient temperature: +40°C
Min. ambient temperature: +10°C
Operating voltage: 400 V / 3-phase / 50Hz
Housing color: epoxy powder coated
Matte textured paint, RAL7035
Dimensions: 562 x 512 x 1073 h mm
Housing type: ECP2-B
Delivery includes:
23-liter collection tank including filler neck and
level sight glass indicator
Submerged copper/aluminium evaporators
2 1 piece 11-04-00210 electronic differential thermoregulator (with
outside temperature sensor), set of 4 for
temperature control and alarm for high
coolant temperature, adjustable in 0.1° C
increments
1° set point, temperature control
2° set point, temperature alarm NC for OK status
(suggested setting >5°K with respect to the
maximum setting value at the 1° set point)
Machine stop if the room temperature is too low:
in an extremely cold environment,
prevents the coolant temperature of the cooler
from adapting (too far) to the ambient temperature
(suggested setting <5°K from the minimum
working temperature of the cooler).
The activation of the cooling function is
forced: in an environment that is too warm, it prevents the cooling medium temperature of the cooler from adapting (too far) to the ambient temperature (suggested setting >5°K from the minimum working temperature of the cooler).
3 1 piece 11-12-00001 Alarms switched separately
4 1 piece 11-00-00028 Remote switching
3 1 piece 11-14-A0614 Electrical control box complete with
main switch, relay, circuit breaker,
motor protection and preparation for alarms. Series connection with NC contact for OK state.
4 1 piece 00-04-00135 Centrifugal pump in stainless steel Inox aisi 304, incl.
pressure gauge with the following properties 50 Hz
* Volume flow 5-30 l/min
* Delivery pressure: 4 - 0.5 bar
* Motor power consumption 580 W
The information refers to the domestic water
5 1 piece 00-09-00038 Hydraulic bypass to protect the pump
8 1 piece 11-11-00002 Level monitor with remote alarm NC for OK status. Design for alarm signal via
remote cable
9 1 piece 15-01-00174 HARTING connector 10-pin complete with connector
(cod. Harting 09 30 010 0303 - 1 lever)
9 1 piece 15-01-00141 Harting connector 4-pin (external probe)
10 1 piece 90-00-00002 Special paint finish "TOTAL":